Frico

SWS323 Fan Heater

Water heat, 400V3

Item number: 4972

Basic fan heater for water connection

Fan heater SWS is intended for water connection. SWS is suitable for places where fan heaters are traditionally used, such as industrial premises, workshops and storage rooms. The fan heater can be mounted on the wall. By turning the unit the water connections will be positioned on the left or right side.

Fan heater SWS has a compact and functional design well suitable for the applications it is intended for.

Technical parameters

Nominal data
Color casing Grey alu-zink
Color, outlet grilles Aluminum / Aluminum
Enclosure class IP44
Ambient working temperature (dry conditions) -20 to 40 °C
Dimensions and weights
Width 830 mm
Height 800 mm
Depth 350 mm
Weight 40 kg
Air flow
Air flow 5890; 4400 m³/h
Sound data
Sound pressure (LpA) 62; 56 dB(A)
Conditions sound pressure Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m².
Sound power (LWA) 77 dB(A)
Conditions sound level Measurements according to ISO 27327-2: 2014, Installation type E.
Motor/control supply
Control/motor supply 400 V
Control/motor current 0.82 A
Input power (P1), motor 430 W
Water data
Water heating full output 80/60 °C, air +15 °C 48 kW
Water heating full output 60/40 °C, air +15 °C 26.9 kW
Pressure drop water 80/60 °C, air +15 °C 9.5 kPa
Pressure drop water 60/40 °C, air +15 °C 3.7 kPa
Water temperature max 150 °C
Maximum working pressure 10 bar
Water volume inside coil 3.8 L
Dimension water connections 28 mm

* For conditions, please see catalogue pages

RFA
DXF

Basic fan heater for water connection.

Application

Fan heater SWS is intended for water connection. SWS is suitable for places where fan heaters are traditionally used, such as industrial premises, workshops and storage rooms. The fan heater can be mounted on the wall or the ceiling. By turning the unit the water connections will be positioned on the left or right side.

Design

Fan heater SWS has a compact and functional design well suitable for the applications it is intended for.

Motor protect. switch S-DT 16 - Frico
Item number: 161206
Motor protect. switch S-DT 16

16A, 400V, IP55, surface-mounting, TK

.
KRT1900 Capillary thermostat - Frico
Item number: 5999
KRT1900 Capillary thermostat

16/10A, 230/400V~, 0°- +40°C, IP55

.
KRTV19 Capillary thermostat - Frico
Item number: 10214
KRTV19 Capillary thermostat

16/10A, 230/400V~, 0°- +40°C IP44, dial

.
SD20 Actuator on/off 230V - Frico
Item number: 10073
SD20 Actuator on/off 230V

VA7010-8103 + adapter M28/M30

.
SWB3 Mounting brackets - Frico
Item number: 17580
SWB3 Mounting brackets

2 pcs, for CPF/SLH/SWH/SWL/SWS32/33

.
SWD3 Return air intake - Frico
Item number: 10103
SWD3 Return air intake

For CPF32/33 SWH32/33 SWS32/33 SWL32/33

.
SWEF3 Extra filter Coarse 50% - Frico
Item number: 10111
SWEF3 Extra filter Coarse 50%

G3, 4 bags, CPF/SWH/SWS/SWL32/33

.
SWF3 Filter section - Frico
Item number: 10117
SWF3 Filter section

For CPF32/33 SWH32/33 SWS32/33 SWL32/33

.
SWLR3 Extra air director - Frico
Item number: 10134
SWLR3 Extra air director

For CPF/SWH/SWS/SWL32/33

.
SWSFT3 Basic filter SWS/L32/33 - Frico
Item number: 27660
SWSFT3 Basic filter SWS/L32/33

Accessory SWS/L32/33

.
SWST3 Drip tray SWS32/33 - Frico
Item number: 111305
SWST3 Drip tray SWS32/33

Accessorie SWS32/33

.
SWYD1 Switch DELTA Y - Frico
Item number: 18034
SWYD1 Switch DELTA Y

For SWS 400V

.
TKS16 Electronic thermostat - Frico
Item number: 11651
TKS16 Electronic thermostat

1-pole switch, alt. cont. 16A 230V~, IP30

.
TRVS20 3-way valve - Frico
Item number: 19019
TRVS20 3-way valve

NO, Body DN15, Connection DN20

.
TRVS25 3-way valve - Frico
Item number: 19020
TRVS25 3-way valve

NO, Body DN20, Connection DN25

.
TVVS20 2-way valve - Frico
Item number: 24729
TVVS20 2-way valve

NO, Body DN15, Connection DN20

.
TVVS25 2-way valve - Frico
Item number: 24730
TVVS25 2-way valve

NO, Body DN20, Connection DN25

.